ANSUL 安素FM200全淹没灭火系统 设计、安装和维护手册(2019英文版).pdf

ANSUL 安素FM-200全淹没灭火系统 设计、安装和维护手册(2019英文版).pdf文档页数:174文档大小:3.04MB文档格式:pdfFIRESUPPRESSIONSYSTEMS FM-200TOTALFLO0DDESIGNINSTALLATIONAND MAINTENANCE MANUALAuthorized ANSULe FM-200TM and SAPPHIREe Engineered System Distribu...

ANSUL 安素FM-200全淹没灭火系统 设计、安装和维护手册(2019英文版).pdf

文档页数:174文档大小:3.04MB文档格式:pdf

FIRESUPPRESSIONSYSTEMS FM-200TOTALFLO0D

DESIGNINSTALLATIONAND MAINTENANCE MANUAL

Authorized ANSULe FM-200TM and SAPPHIREe Engineered System Distributors

FROM: Product Management - Engineered Systems

SUBJECT: New Electric Actuator for ANSUL: SAPPHIRE and FM-200 Systems

Johnson Controls is pleased to introduce the UL ListedFM Approvedand LPCB Redbook ListedElectric Actuator(Part No. 304205030) for both SAPPHIRE and FM-200 Fire Suppression Systems. The new design of the electric

FIGURE1ELECTRIC ACTUATOR (Part No. 304205030) 010684

the permanent magnet and allows the spring to push and latch the actuator pin into the fire position. The service lifeof the electric actuator has been extended to 25 years.

This bulletin serves as an addition to the following UL/FM approved manuals and wilbe added to the manuals at the next update.

October 92015 ANSULe SAPPHIRE SystemDesignInstallationand Maintenance Manual (Part No. 57059O) datedSeptember 12010 ANSUL? SAPPHIRE SystemDesignInstallationand Maintenance Manual (India Version --Part No. 570805) dated September 2015

One Stanton Street MarinetteWI 541432542

Bulletin No. 2018265May 132019 Page 2

Third party approvals cover the following system operating conditions:

25 Bar FM-200 32°F to 130 °F(0 °℃ to 54 °℃)25 Bar SAPPHIRE32°F to 130°F(0°℃ to 54 °℃)

Electric ActuatorTechnical Specifications are asfollows:

Body Finish Electroless Nickel Plate Mild SteelActuator Pin Stainless SteelConnection 1 in.BSPPElectrical Connection 1/2 in. NPT (F) conduit connection

These installation instructions are intended for use with the Electric Actuator (Part No. 304205030). Personnelbefore attempting to install or service any electric actuator.

Bulletin No. 2018265May 132019 Page 3

AWARNING

The fire suppression system could actuateintroducing a potentially hazardous environmentcausing instructions and follow them carefully during installation.

INSTALLATION

panel which has been qualified for releasing device service. The UL Listed fire alarm control panel shallhave been Installation of the electric actuator shall be to the supervised releasing device circuit of a UL Listed fire alarm controlUL Listed fire alarm control panel manual for information on allowable device patibility. found patible for use with the electrical actuator (Part No. 304205030) covered in this Bulletin. Reference the

Install the electric actuator to the top of the valve assembly as follows:

1. Ensure the electric actuator pin is in the non-fired position by fully screwing in the reset tool0.27 in. (6.85 mm).2. Remove the dust cap from the top of the discharge valve assembly.3. Carefully thread the electric actuator onto the discharge valvebetween the valve and manualactuatoruntil handl-tight.

ud o p iu) n s ud nsu pue ( a pn)n

ACAUTION

container to actuate.

actuator.

4. Wiring the actuator to the releasing circuit of the UL Listed Fire Alarm Control Panel:30 mA. The conduit connection on the electric actuator is 1/2 in. NPT (F)

For the release circuit

a. Using threaded conduit connection on the electric actuatorpulleads through to a junction box to makeb.Connect Positive from the release circuit to either the black or white lead wire. connections.Note: Actuator contains bridge rectifiertherefore polarity can be reversed.c.Connect Negative from the release circuit to the opposite lead from step 2.d.Installthe in-line supervisory device into the circuit if required. (Refer to control panel instructions.)

For the placement indicator circuit (supervised)

a.Using threaded conduit connection on the electric actuatorpulleads through to a junction box to makeconnections.b.Connect Positive from the input circuit to either one of the yellow or orange pairs.c.Connect Negative from the input to the opposite lead from step b. d. Of the remaining yellow and orange wireplace the End-of-Line resistor (EOL). (Refer to control panelinstructions for appropriate value.